0.6/1kv Cu/PVC / STA/PVC Power Cable
0.6/1kV Cu Conductor PVC Insulated Steel Tape Armored PVC Sheathed Power Cable
Standard:
It is manufacture under GB/T12706-2002 standard(The same as IEC60502).
Application:
It is used to transmit and distribute power on the power line of A. C. Rated voltage 0.6/1kV.
Using features:
1. Rated voltage: Uo/U: 0.6/1kV
2. No. Of core: Single-core, Two-core, Three-core, Four-core, Five-core
3. The highest allowed operating temperature of conductor for long-term working is 70oC. In short-circuit (Max. Long-term is no more than 5 seconds). The highest temperature for conductor is no more than 160oC.
4. D. C. Resistance of the conductor complies with the stipulations of GB/T3956-1997.
5. The environment temperature should be no lower than 0oC when lay. Otherwise it should be preheated.
7. Working Frequency Voltage Test: 2.5Uo+2kV/5min without puncture.
Note:
The single core armoured cables are used for D. C. System only. If used for A. C. System, the magnetic isolation should be applied on the steel armoire wires of non-magnetical materials should be used.
0.6/1kv Cu/PVC / STA/PVC Power Cable product offered by Xingle Group Limited Company