Product Description
330KV SF6 CIRCUIT BREAKERS WITH SPRING OPERATING
MECHANISM
S/NO. | PARAMETER DESCRIPTION | UNIT | PERFORMANCE GUARANTEE |
330KV SF6 CB |
1 | Scope: Design, manufacture, testing, supply & installation. | | Yes + Supervision by accredited personnel |
2 Design & Construction | | |
2.1 | Type designation | | |
2.2 | Reference Standard | | IEC 62271-100 IEC 62271-1 |
2.3 | No. of poles/circuit breakers | | 3 |
2.4 | Type of control mechanism | | Motor operated spring |
2.4.1 | Mechanical class | | M2 |
2.5 | Protection level of electrical cubicle | | IP54 |
2.6 | Protection level of operating mechanism | | IP55 |
2.7 | Type of and colour insulator | | Porcelain, brown |
2.8 | Insulating gas | | SF6 |
2.9 | Rated absolute pressure at 20oC | | |
2.10 | Relative leakage rate | %/yr | 0,5% |
2.11 | Circuit breaker class | | Outdoor |
2.12 | Support structures supplied | | Yes |
3 Service Conditions | | |
3.1 | Altitude of installation | m | 1300 |
3.2 | Operating ambient temperature | oC | -1 to +40 |
3.3 | Relative humidity | % | 80 |
3.4 | Pollution levels | mm/kV | 25 |
4 Rated Characteristics | | |
4.1 | Rated voltage | kV | 330 |
4.2 | Maximum service voltage | kV | 362 |
4.3 | Rated frequency | Hz | 50 |
4.4 | Rated continuous current | A | 4000 |
4.5 | Rated peak withstand current | kApk | 125 |
4.6 | Rated short time withstand current | kA | 50 |
4.7 | Rated duration of short circuit | s | 3 |
4.8 | One min. power frequency withstand voltage: | | |
| - phase to earth | kV | 450 |
- Across open contacts | kV | 520 |
4.9 | Rated lightning impulse withstand voltage: | | |
| - phase to earth | kVpk | 1175 |
- across open contacts | kVpk | 1175 (+205) |
4.10 | Rated switching impulse withstand voltage: | | |
| - phase to earth | kVpk | 950 |
- across open contacts | kVpk | 800 (+295) |
5. Breaking and Making Characteristics | | |
5.1 | Rated short circuit breaking current | kA | 50 |
5.2 | First pole to clear factor | | 1.3 |
5.3 | DC component (% of AC component) | | 50 |
5.4 | Peak value of rated short circuit making current | kApk | 125 |
5.5 | Rated breaking current for short line faults | | As per IEC Standard |
5.6 | Rated out of phase breaking current | Id (kA) | 12,5 |
5.7 | Rated overvoltage factor for unloaded transformers | | 2.5 |
5.8 | Rated line charging breaking current | A | 255 |
5.9 | Rated cable charging breaking current | | 355 |
6. Operating Times | | |
6.1 | Rated opening time - from opening coil energizing to separation of main contacts | ms | 24 |
6.2 | Rated breaking time - from opening coil energizing to arc extinction | ms | 40 |
6.3 | Rated closing time - from closing coil energizing to main contact making | ms | 110 |
6.4 | Rated operating sequence | | O-0.3s-CO-15s-CO |
6.5 | Rated operating sequence without motor supply | | O-CO |
7. Low Voltage Specification | | |
7.1 | Motor voltage | V | 220, DC |
7.2 | Circuit motor protection | | MCB |
7.3 | Motor voltage min. range | % | 85 |
7.4 | Motor voltage max. range | V | 220, DC |
7.5 | Opening voltage min. range | % | 65 |
7.6 | Opening voltage max. range | % | 110 |
7.7 | Closing voltage min. range | % | 75 |
7.8 | Closing voltage max. range | % | 110 |
7.9 | Lighting and heating circuit voltage | V | 220, AC |
7.10 | Local electrical control with two push button | | Yes |
7.11 | Anti-pumping relay | | Yes |
7.12 | Local/remote selector switch | | Yes |
7.13 | Number of trip coils | | 2 |
7.14 | Provision for trip coil supervision | | Yes |
7.15 | Pole discrepancy feature | | Yes |
7.16 | Signalling contacts for spring position | | Yes, 1NO |
7.17 | Number of available auxiliary NO contacts | | 8 |
7.18 | Number of available NC auxiliary contacts | | 8 |
7.19 | Position indicator - O/I | | Yes |
7.20 | Indicator for spring status | | Yes |
7.21 | Gas for first filling plus 30% | | Yes |
7.22 | SF6 filling equipment supplied | | Yes |
7.23 | SF6 gas leakage detector supplied | | Yes |
8. Documents and Drawings with Bid | | |
8.1 | Circuit breaker outline drawing | | Yes |
8.2 | Foundation detail drawings | | Yes |
8.3 | Quality assurance certification | | Yes |
8.4 | Typical low voltage elementary diagram | | Yes |
9. Test Reports with Bid | | |
9.1 | Dielectric test | | Yes |
9.2 | Temperature rise test | | Yes |
9.3 | Short time withstand current test | | Yes |
9.4 | Mechanical endurance test | | Class M2 - 10,000 operations |
9.5 | Capacitive current breaking test | | Yes |
9.6 | Operating times test | | Yes |
9.7 | Main contact resistance test | | Yes |
Ningbo Hyuan Power Industry Co., Ltd was found in 2006, It is a professional company which is involved in Complete supply, Designing, Consulate and Service of Substation up to 245kv and of Distribution Automation up to 245kv
Our product is including of:
1.15KV/27KV/38KV, 50Hz/60Hz, 630A/1250A The Most advanced Recloser in the world for Pole mounted and Substation Mounted with Protocol IEC61850/DNP3.0 according to IEEE/ANSI/IEC standard;
2.15KV/27KV/33KV/66KV/123KV/145KV/150KV/170KV/245KV, 50Hz/60Hz, 1250A/2000A/3150A, Three phase Outdoor Isolator/Disconnector with Double Break at side /Central Single Break for Level/Vertical Mounted on Pad Substation or Power Tower;
3.15KV/27KV/33KV/66KV/123KV/145KV/150KV/170KV/245KV, 50Hz/60Hz, 1250A/2000A/3150A, Outdoor Three phase /Single phase SF6/Vacuum Circuit Breaker with Three Phase Common Operation /Single Phase Seperate Operation;
4.15KV/27KV/38KV/66KV/123KV/145KV/150KV/245KV, 50Hz/60Hz, MR2000/1(5)A, Outdoor Oil/Resin/Capacitor Current transformer, Voltage Transformer up to 5 cores;
5.15KV/27KV/38KV/66KV/123KV/145KV/150KV/245KV, 50Hz/60Hz, 100kvar to 100Mvar capacitor bank for pad mounted and Pole mounted;
6.15KV/27KV/38KV/66KV/123KV/145KV/150KV/245KV, 50Hz/60Hz Power Transformer up to 200mva and reactor up to 200Mvar;
7.400V/6KV/15KV/27KV/38KV, 50Hz. 60Hz, indoor AC control and Protection switchgear panel for substation and Distribution system;
8.48VDC/110VDC/220VDC 50Hz/60Hz Lead-Acid/Ni-CD Battery bank with Charger up to 2000AH;
9.15KV/27KV/38KV/66KV/123KV/145KV/150KV/245KV, 50Hz/60Hz Cable heat srink/cold shrink Terminal and Joint with joint box
10.33KV/66KV/145KV 50Hz/60Hz dead tank GCB /HGIS and compact GIS;
11.11KV/33KV, 50Hz/60Hz, 9/11/17/32 steps ON LOAD TAP CHANGER for Power Ttansformer
12. RTU remote terminal unit for VCB, SWITCHGEAR AND RECLOSER WITH IEC61850/DNP3.0 Protocol
Our Mian service is including of:
1. Designing, Complete Supply, Conssate and Commission of 33KV/66KV/145KV/245KV 60Hz/50Hz substation including of GCB, DS, CT PT, LA, Transformer, Cable, Control & Protection Panel, Earthing Grounding system,
SCADA system, Steel grid tower;
2. Desinging, Complete Supply, consulate and Commission of 33kv/66kv/145kv/230kv 60Hz/50Hz Distribution automatic system including of recloser, sectionaliser, fault indicator, RTU, GPRS, and management software
We are rich experience in substation and automatic distribution system for 10years, our business had been involve in the world I including of Bangladesh, Indonesia, malasia, Pakistan, zimbia, zembewei, Peru, Ecuador ect over the world.
Customerizer will be welcome, Speciall required wil be welcome, we have good experience to proposal you and support you to success in business.
All the goods from HEMG will be guaranteed within 2 years, in specially, it will be 5 years.
For Above 1 million Order, We will send our engineer to work in site untill runing in good conditions.
More >
Other Products with This Manufacturers